DO Removal by Partial Vacuum
Purpose and Principle
The purpose of this experiment was to determine the degree of dissolved oxygen removal from supersaturated water subject to a partial vacuum. Dissolved oxygen removal from the water occurs because the partial pressure of oxygen in space above the water was lowered by the partial vacuum. Thus, the dissolved oxygen would transfer out to the space above the water in order to restore equilibrium as stated in Henry's Law. Measuring the dissolved oxygen in the water over a period of time allowed us to observe the amount of dissolved oxygen removed and also to calculate the approximate rate of dissolved oxygen removal.
Procedure
We started the experiment by calibrating the dissolved oxygen probe and pressure sensor. This was done by vigorously aerating the water in the apparatus without the lid on for around 5 minutes to get the water to equilibrium DO saturation. This level of DO was set in EasyData to be 8.7 mg/L which is nearly the value of 100 percent oxygen saturation of pure water at atmospheric pressure. While using EasyData to monitor the pressure and dissolved oxygen, water originating from the large container above the sink filled with tap water was pumped out of the apparatus until the desired pressure was reached. The water was at around 20 degrees centigrade and constantly stirred. Once the desired pressure was attained, the pump was stopped and the apparatus was
Objectives
Procedure
The procedure for this experiment is relatively simple. While using Easy Data to monitor the pressure, water is pumped out until the pressure reaches -50 to -70 kPA. The apparatus is allowed to sit for a short period of time and is then opened to atmospheric pressure and the dissolved oxygen is monitored and recorded for no more than two minutes. We wish to see a drop of at least 2 mg/L in that period of time.
Results and Discussion
From our experiments, we have found that the change in dissolved oxygen that occurs over the span of a few minutes is less than desirable. We ran experiments that involved aerating water under a partial vacuum and compared the results to data obtained from experiments in which water was only subject to a partial vacuum with no aeration. We were expecting to see a greater change in the dissolved oxygen concentration; however, contrary to our initial belief, aerating the water had little affect on the change in dissolved oxygen. Because of this, we are doubtful that the aeration method will solve the floating flocs problem and have decided to consider alternate solution methods. While we search for other possible solutions, we will still continue to run quick experiments with the aeration method in order to verify our decision to move to an alternate solution.
time. This time was varied to determine, after being converted from time to distance based on a influent water velocity of 740 m/day, what the optimal vertical pipe length would be using our system. These values varied from seconds to a few minutes representing a pipe length of a fraction of a meter to a few meters. The system was then opened to the atmosphere by releasing the clamp on the pump that constricted the tube leading out of the apparatus. The dissolved oxygen was monitored and recorded for two to three minutes after this.
Results and Discussion
| Wiki Markup |
|---|
{float:left|border=2px solid black|width=350px}
Click graphs to see larger.
{anchor: Figure 1}
[!E1T1DOVac.PNG|width=350px!|Experiment 1 Test 1 Results]
h5. Figure 1: Experiment 1 Test 1, DO behavior under partial vacuum.
{anchor: Figure 2}
[!E1T1PressureVac.PNG|width=350px!|Experiment 1 Test 1 Results]
h5. Figure 2: Experiment 1 Test 1, Pressure conditions under partial vacuum.
{anchor: Figure 3}
[!E1T1DOatm.PNG|width=350px!|Experiment 1 Test 1 Results]
h5. Figure 3: Experiment 1 Test 1, DO behavior at atmospheric pressure.
{float} |
| Wiki Markup |
|---|
{float:left|border=2px solid black|width=350px}
Click graphs to see larger.
{anchor: Figure 4}
[!E1T2DOVac.PNG|width=350px!|Experiment 1 Test 2 Results]
h5. Figure 4: Experiment 1 Test 2, DO behavior under partial vacuum.
{anchor: Figure 5}
[!E1T2PressureVac.PNG|width=350px!|Experiment 1 Test 2 Results]
h5. Figure 5: Experiment 1 Test 2, Pressure conditions under partial vacuum.
{anchor: Figure 6}
[!E1T2DOVac.PNG|width=350px!|Experiment 1 Test 2 Results]
h5. Figure 6: Experiment 1 Test 2, DO behavior at atmospheric pressure.
{float} |
Graphs from two tests can be seen above. #Figure 1 and #Figure 3 depict the behavior of the dissolved oxygen concentration under negative pressure conditions profiled in #Figure 2 and #Figure 5 for test 1 and test 2, respectively. #Figure 3 and #Figure 6 show the change in dissolved oxygen concentration after the reactor was opened to the atmosphere.
The charts above both indicate a change in dissolved oxygen of about 0.3 mg/L over a minute to two minutes for water subject solely to partial vacuum. For the first test, the water was subject to a pressure drop from atmospheric to approximately -70 kPa. A total pressure drop of -70 kPa was also used in the second test though the water was kept at approximately -37 kPa for about a minute in order to observe the effect of this pressure on the dissolved oxygen. It can be seen by juxtaposing the two curves on the same plot (#Figure 7) that the behavior of dissolved oxygen after being exposed to the partial vacuum are fairly similar. The first test was performed with a higher initial dissolved oxygen content in the water, so the graph is positioned slightly higher than the second test curve.
| Anchor | ||||
|---|---|---|---|---|
|
| Wiki Markup |
|---|
{float:left|border=2px solid black|width=600px}
!E1T1T2Comparison.PNG|width=600px!
h5. Figure 7: Graph comparing DO curves from Test 1 and Test 2.
{float} |
Also, the increase in dissolved oxygen concentration post vacuum was likely due to reincorporation of oxygen from tiny bubbles that formed on the interior walls of the reactor that were unable to float out of the reactor.
Using this data as a baseline, a second experiment was run in which the water was aerated under partial vacuum and is described in DO Removal by Partial Vacuum and AerationSome of the major concerns about our data include discrepancies caused by erratic behavior of the dissolved oxygen probe under partial vacuum. We are still trying to understand what might be causing the discrepancies and to what degree the functionality of the probe is affected. We are concerned that after the probe is subject to negative pressure, data collected after pressurization may be faulty. In the mean time, we will be measuring dissolved oxygen before and after pressurization and aeration instead of during the process. Also, we were initially concerned about the gradual pressure increase in our system. So, we tested the apparatus to make sure that it was airtight by putting the container under positive pressure and holding it over night. It proved to be airtight enough for our purposes. We postulated that the change in pressure is mostly due to bubbles leaving the solution.